The eLLK 92 Ex-protected light fittings for bi-pin
fluorescent lamps are fitted with an electronic
ballast and conform to the ATEX Directive
94/9/EG. The modern economical ballast
EVG 05 according to the latest standards
(IEC 60079-7: 2006) allows a safe and econo -
mical operation of bi-pin fluorescent lamps
G13 according to IEC 60081. Lamps reaching
its end of life will be monitored and securely
switched off (EOL-effect). The high input voltage
range allows international use. Due to the
standard dual channel architecture (with double
lamp fittings) if one fluorescent lamp fails, the
other fluorescent lamp will independently stay
in operation. The standard single-sided throughwiring
in connection with the variety of possi -
bilities offers a cost efficient installation. Doublesided
lock with 10, 20 or 24 latch points allows
the protective bowl to be hingeable on both
sides meaning the fitting can be mounted
without having to pay attention to which side is
the right side. Automatic switch built as a safety
disconnector according to EN 60947 (IEC 664)
with an automatic switch ensuring the disconnection
of all exposed components when the
fitting is opened. The optional CG-S module
represents an optimum solution for the individual
monitoring of light fittings connected to CEAG
emergency battery systems.
• Protection: Ex de IIC T4, IP66 / Ex tD A21 IP66 T80 °C
• Permissible ambient temperature: -25°C to +55°C
• Lamps: G13 1x18W, 2x18W, 1x36W, 2x36W, 1x58W, 2x58W
• Power factor cosφ: ≥ 0.95
• Frequency: 50 - 60Hz
• Enclosure material: Glass-fibre reinforced polyester